首页   按字顺浏览 期刊浏览 卷期浏览 Mechanism and effects of ozone treatment for cooling water system
Mechanism and effects of ozone treatment for cooling water system

 

作者: Shu‐Hai You,   Dyi‐Hwa Tseng,   Gia‐Luen Guo,   Shin‐Yi Lee,  

 

期刊: Journal of Environmental Science and Health, Part A  (Taylor Available online 2000)
卷期: Volume 35, issue 1  

页码: 87-107

 

ISSN:1093-4529

 

年代: 2000

 

DOI:10.1080/10934520009376956

 

出版商: Taylor & Francis Group

 

关键词: Oxidative film;cooling water;ozone treatment;corrosion control;scale control;microorganism control

 

数据来源: Taylor

 

摘要:

The sole ozone used in cooling water treatment has raised some critical questions concerned with what happens chemically, that may describe why it can control corrosion, scale and microorganism. The pilot cooling tower (PCT) test presented the effects of ozone as a sole cooling water treatment. Except the higher pH and alkalinity in the PCT test, proper residual ozone concentration produced an oxidative film (protective film) on the metal surface of carbon steel, brass and type 316 stainless steel, the corrosion rate may also be decreased. Ozone was still unpredictable for scale control except for the existence of organic matter. The excellent control of fouling was also attained, that could be determined by the presence of ozone. The strong biocide properties of ozone resulted in excellent biological control. A mechanism is proposed to explain the results.

 