首页   按字顺浏览 期刊浏览 卷期浏览 Some observations on oil deterioration in transformers and switchgear
Some observations on oil deterioration in transformers and switchgear

 

作者: H.Hurworth,  

 

期刊: Journal of the Institution of Electrical Engineers - Part II: Power Engineering  (IET Available online 1948)
卷期: Volume 95, issue 45  

页码: 328-336

 

年代: 1948

 

DOI:10.1049/ji-2.1948.0080

 

出版商: IEE

 

数据来源: IET

 

摘要:

It is suggested that the early stages of oil deterioration progress at a rate which has the characteristics of autocatalysis. This is followed by a prolonged period during which the rate is controlled by the partial pressure of oxygen in the atmosphere. It is shown that the period of autocatalytic acceleration can be shortened by slightly modifying the design of transformers, thus increasing the useful life of the oil. Tests are described which indicate the amount of improvement likely to be gained.Attention is also directed to the behaviour of oil vapour under electrical stress, and to the large quantities of acid and sludge sometimes produced as a result of stress from live conductors, terminals and insulators projecting above the oil surface.

 

点击下载:  PDF (1341KB)