首页   按字顺浏览 期刊浏览 卷期浏览 Calculation of errors in three-winding voltage transformers
Calculation of errors in three-winding voltage transformers

 

作者: T.Waterhouse,  

 

期刊: Journal of the Institution of Electrical Engineers - Part II: Power Engineering  (IET Available online 1948)
卷期: Volume 95, issue 43  

页码: 71-78

 

年代: 1948

 

DOI:10.1049/ji-2.1948.0010

 

出版商: IEE

 

数据来源: IET

 

摘要:

Voltage transformers having two secondary windings for connection to dual instrument burdens are discussed. After considering the vector diagrams under no-load and under load conditions, expressions are derived which enable the performance to be predetermined from the design data of the transformer. The influence of the burden on one of the secondary windings in modifying the errors at the terminals of the other secondary winding is investigated. From the analytical equations, further expressions are deduced to facilitate the estimation of the performance of a transformer when the results of standard tests are given. Finally, the calculated and measured errors of two transformers under various loading conditions are compared and are shown to agree.

 

点击下载:  PDF (899KB)