首页   按字顺浏览 期刊浏览 卷期浏览 New balance ground relay for parallel four‐circuit transmission lines
New balance ground relay for parallel four‐circuit transmission lines

 

作者: Takaaki Kai,   Shizuo Nomura,   Takeshi Ando,  

 

期刊: Electrical Engineering in Japan  (WILEY Available online 1992)
卷期: Volume 112, issue 1  

页码: 11-24

 

ISSN:0424-7760

 

年代: 1992

 

DOI:10.1002/eej.4391120102

 

出版商: Wiley Subscription Services, Inc., A Wiley Company

 

数据来源: WILEY

 

摘要:

AbstractA 66‐kV network generally is grounded through a neutral grounding resistor. In this network a single‐phase ground‐fault current is limited to as small as 100 to 400 A. There are parallel four‐circuit transmission lines mounted on the same tower in the 66‐kV network. In such transmission lines, the load and the fault currents could induce circulating current that flows through the lines. Since the circulating current has zero‐phase‐sequence and negative‐phase‐sequence components, it could cause unwanted operation of a balance ground relay using zero‐phase‐sequence current. However, it is difficult to compensate for the circulating current by the conventional vector compensation scheme.This paper presents a new balance ground relay to deal with the circulating current. In the relay from the ground‐fault inception until first tripping, the difference current Δ3I2dof negative‐phase‐sequence current 3I2dof the differential current between two protected lines is used as an input current. The Δ3I2dis the difference current of 3I2dbetween, before and during faults. After the first tripping, the difference current of positive‐phase‐sequence load current and zero‐phase‐sequence current of the forementioned differential current are used as an input current. Consequently, a higher sensitivity of the ground‐fault protection for these lines has been achieved. The correct operation of the new balance ground relay was confirmed when a single‐phase‐ground‐fault occurred in the parallel four‐circuit tr

 

点击下载:  PDF (1148KB)



返 回