Increasing Diesel Start Time for a Boiling Water Reactor (BWR/6) Using the New Emergency Core Cooling System Approach

 

作者: MuralidharanR.,   ChexalV. K.,  

 

期刊: Nuclear Technology  (Taylor Available online 1987)
卷期: Volume 78, issue 1  

页码: 13-23

 

ISSN:0029-5450

 

年代: 1987

 

DOI:10.13182/NT87-A34004

 

出版商: Taylor&Francis

 

数据来源: Taylor

 

摘要:

The emergency core cooling systems (ECCSs) at a reactor site have a dual power source for their assured operation if and when needed. The normal power source is the off-site ac power. In the unlikely event of loss of all off-site power, emergency diesel generators (DGs) are the backup ac source. Thus, there is an incentive to ensure that the reliability of DGs at operating plants is maintained at an acceptable level. A potential contributor to observed diesel degradation is the fast start and loading interval (∼10 s) demanded of the emergency DGs. Such fast start intervals result from the performance required of the ECCS to meet the U.S. Nuclear Regulatory Commission (NRC) acceptance criteria for a hypothetical large-break loss-of-coolant accident (LOCA) (design basis accident) concurrent with a loss of off-site power. The guidelines established by the NRC for the ECCS performance evaluation, which are stated in Appendix K of 10CFR50, have several built-in arbitrary conservatisms. Recently, the NRC outlined in SECY-83-472 a new approach for performing ECCS analysis and has given approval to General Electric to use this new approach in their SAFER/GESTR LOCA analysis computer code. The sensitivity of peak cladding temperature (PCT) is determined using the new realistic LOCA analysis approach for various DG start durations. A quantitative assessment of the various diesel start durations using NRC licensing assumptions was made to determine the impact on the PCT. The results for a boiling water reactor (BWR/6) show that when using licensing assumptions and the SAFER/GESTR code, the PCT that is determined during a design basis LOCA for the present 10-s DG start criteria is∼593°C. This is far below the prescribed limit of 1204.4°C. The results also show that the PCT varies only a small amount with diesel start times of 10 to 30 s. Thus, the diesel start time for the class of reactors analyzed in this study could be changed from 10 to 30 s without the loss of any LOCA safety margin. The results further show that for an 871.1°C PCT, which is the current NRC-approved SAFER application PCT limit, the DG start time can be 70 s (compared to the present specified 10 s). The DG start time could be increased to 118 s when and if, in the future, the SAFER code is qualified to a PCT limit of 1204.4°C for licensing calculations. This work is of interest to nuclear utilities as a means of increasing operational flexibility and to help improve diesel reliability.

 

点击下载:  PDF (1044KB)



返 回