The measurement of water in power transformers
作者:
A.W.Stannett,
期刊:
Proceedings of the IEE - Part A: Power Engineering
(IET Available online 1962)
卷期:
Volume 109,
issue 3S
页码: 80-85
年代: 1962
DOI:10.1049/pi-a.1962.0014
出版商: IEE
数据来源: IET
摘要:
Power transformers are likely to break down at service voltage due to excessive water in the solid insulation. It is shown that insulation measurements between the transformer terminals and tank do not give a reliable indication of the condition of the solid insulation of a transformer in service. It is suggested that a paper probe or image would give the required information. A design of probe is described and some test results are given.A simple method of measuring the degree of water saturation of oil is described in an Appendix.
点击下载:
PDF
(755KB)