首页   按字顺浏览 期刊浏览 卷期浏览 Use Of Static Mixer For Oxidation And Disinfection By Ozone
Use Of Static Mixer For Oxidation And Disinfection By Ozone

 

作者: Nathalie Martin,   Catherine Galey,  

 

期刊: Ozone: Science & Engineering  (Taylor Available online 1994)
卷期: Volume 16, issue 6  

页码: 455-473

 

ISSN:0191-9512

 

年代: 1994

 

DOI:10.1080/01919512.1994.10555754

 

出版商: Taylor & Francis Group

 

关键词: Ozone;Ozone Contacting;Static Mixer;Drinking Water Treatment;Disinfection;Oxidation;Advanced Oxidation;Ozone/Hydrogen Peroxide;“CT” Calculations;Atrazine Destruction;Simazine;Pesticides Oxidation;Ozone Mass Transfer Coefficient;Melun Arvigny

 

数据来源: Taylor

 

摘要:

Ozone is used in drinking water treatment as a biocide, as an oxidant and as a pretreatment in order to improve the performance of subsequent processes. Increasing concern over the quality of drinking water has led to a number of new stringent regulations in the control of chemical and microbiological contaminants. Disinfection deals with the concept of “CT”, which is the need to maintain a certain minimum concentration for a given time. Under ideal laboratory conditions, it is 0.4 mg O3/L for 4 min. In practice, since the method for the CT determination has not been finalized by the EPA, “T” can be the minimum detention time of 90% of total flow, and “C” can be a measured ozone residual at the outlet of cells of the contactor. New standards for micropollutants in drinking water imply an optimization of the ozonation step, by improving the ozone transfer from gas to water, and the control of the detention time as well as ozone residual within the contactor.

 

点击下载:  PDF (574KB)



返 回