首页   按字顺浏览 期刊浏览 卷期浏览 Contamination of the Medical Air Supply with OxygenA Clinical Engineering Incident inve...
Contamination of the Medical Air Supply with OxygenA Clinical Engineering Incident investigation

 

作者: W.,   KANE J.,   RIDLEY M.,   SHEEHAN G.,  

 

期刊: Journal of Clinical Engineering  (OVID Available online 1990)
卷期: Volume 15, issue 4  

页码: 295-300

 

ISSN:0363-8855

 

年代: 1990

 

出版商: OVID

 

数据来源: OVID

 

摘要:

Two incidents of oxygen contamination. in the hospital medical air supply occurred on consecutive weekends. This paper describes those incidents and the investigation that followed. The cause of the contamination was determined to be faulty, check values in some Bird air/oxygen blenders. The investigation of the incidents was hindered because the conventional blender test methods did not detect the problem. Only after monitoring the medical air and oxygen pressures and simulating the real conditions did the cause of the problem surface.

 

点击下载:  PDF (396KB)