Heat transfer from a buoyant smoke layer beneath a ceiling to a sprinkler spray. 2—an experiment
作者:
H. P. Morgan,
K. Baines,
期刊:
Fire and Materials
(WILEY Available online 1979)
卷期:
Volume 3,
issue 1
页码: 34-38
ISSN:0308-0501
年代: 1979
DOI:10.1002/fam.810030107
出版商: Heyden&Son Ltd.
数据来源: WILEY
摘要:
AbstractAn experiment is described which measures the heat transferred from a hot, flowing, buoyant gas layer in a mall, to a sprinkler spray. Interpolation techniques are described which allow for the large heat losses occurring within the apparatus (a large‐scale model mall). The results are compared with predictions based on the method developed in Part 1 and found to be consistently 150% of the predicted heat transfer rates. Given the assumptions required by the predictive calculations this is thought to be reasonable degree of agreement. The largest heat transfer rate to the one sprinkler spray in this experiment was 157 kW ± 38