首页   按字顺浏览 期刊浏览 卷期浏览 Performance of distance protection applied to underground cables alone or mixed with ov...
Performance of distance protection applied to underground cables alone or mixed with overhead lines

 

作者: M.M.El-Kateb,  

 

期刊: Proceedings of the Institution of Electrical Engineers  (IET Available online 1979)
卷期: Volume 126, issue 9  

页码: 805-814

 

年代: 1979

 

DOI:10.1049/piee.1979.0254

 

出版商: IEE

 

数据来源: IET

 

摘要:

The unequal impedance angles of the positive and zero sequence underground-cable impedances, which are in variance with overhead lines, requires a study to evaluate the appropriate relay residual compnesation factor, which is of paramount importance for earth faults. The problem, in many cases, is provoked when the protected zone consists of a mix of underground cables and overhead lines. This paper shows the importance of having an accurate residual vectorial compensation together with a proper selected comparator characteristic.

 

点击下载:  PDF (1274KB)