首页   按字顺浏览 期刊浏览 卷期浏览 Errors in power-factor measurement due to terminal losses on short lengths of cable
Errors in power-factor measurement due to terminal losses on short lengths of cable

 

作者: R.A.Brockbank,  

 

期刊: Journal of the Institution of Electrical Engineers  (IET Available online 1932)
卷期: Volume 70, issue 422  

页码: 281-292

 

年代: 1932

 

DOI:10.1049/jiee-1.1932.0022

 

出版商: IEE

 

数据来源: IET

 

摘要:

It is frequently necessary for economic reasons to carry out tests on short cable samples. Measurements of a.c. leakance and power factor on short lengths of power or submarine cables may be subject to considerable error unless due allowance is made for end effects, which are of minor importance on long lengths. The application of the simple guard wire, which is adequate for d.c. testing, is not sufficient to secure accurate results. The nature of the errors which arise is discussed, a theory of the cause of the errors is developed, and recommendations are made as to the form of guard which will enable accurate results to be obtained.

 

点击下载:  PDF (1203KB)