首页   按字顺浏览 期刊浏览 卷期浏览 Characteristics of impulse breakdown of standard rod gaps under controlled-atmosphere c...
Characteristics of impulse breakdown of standard rod gaps under controlled-atmosphere conditions

 

作者: J.E.Matthews,   R.Saint-Arnaud,  

 

期刊: Proceedings of the Institution of Electrical Engineers  (IET Available online 1971)
卷期: Volume 118, issue 10  

页码: 1524-1527

 

年代: 1971

 

DOI:10.1049/piee.1971.0279

 

出版商: IEE

 

数据来源: IET

 

摘要:

The effect of humidity, polarity and irradiation on the 1/50μs impulse voltage breakdown and time lag of standard rod gaps has been determined for a range of spacings from 5cm to 30cm and a range of humidities from 1g/m3to 24g/m3. An anomalous condition is reported for a 5cm unirradiated gap under positive impulses in which the slope of the humidity characteristic is opposite to that normally obtained. It is shown that, although the time lag is independent of humidity, the probability of breakdown in the sigmoid region is not independent of humidity.

 

点击下载:  PDF (611KB)