Effect of load characteristics and voltage-regulator speed-stabilising signal on power-system dynamic stability
作者:
N.D.Rao,
S.C.Tripathy,
期刊:
Proceedings of the Institution of Electrical Engineers
(IET Available online 1977)
卷期:
Volume 124,
issue 7
页码: 613-618
年代: 1977
DOI:10.1049/piee.1977.0131
出版商: IEE
数据来源: IET
摘要:
It has been recognised that the dynamic-stability margin of synchronous generators can be improved by the damping effect of the speed-stabilising signal in the excitation control system. The dynamic-stability analysis is extended to account for the effect of loads modelled as a nonlinear function of voltage. In order to make the analysis realistic, a conventional load-frequency control system is also considered to be regulating the power-system frequency and tie-line power. The load voltage is considered to be undergoing changes in the dynamic period in response to speed signal in the excitation system which establishes a coupling betweenQVand p.f. control loops. The damping effect on frequency and tie-line power oscillations is studied by varying the load characteristics and excitation stabiliser parameters.
点击下载:
PDF
(751KB)
返 回