首页   按字顺浏览 期刊浏览 卷期浏览 Improved methods of test for the insulation of electrical equipment
Improved methods of test for the insulation of electrical equipment

 

作者: G.Mole,  

 

期刊: Proceedings of the IEE - Part IIA: Insulating Materials  (IET Available online 1953)
卷期: Volume 100, issue 3  

页码: 276-283

 

年代: 1953

 

DOI:10.1049/pi-2a.1953.0040

 

出版商: IEE

 

数据来源: IET

 

摘要:

An improved method of testing paper insulation for moisture by the measurement of dielectric dispersion over the frequency range 0.5–50 c/s or over the time range 3–300 millisec has been investigated. A direct-reading portable instrument giving immediately-significant results has been developed for dispersion testing, and its suitability for the testing of paper-insulated bushings, busbars, transformers and cables is now under investigation. An alternative method of detecting moisture in paper insulation which has been examined is the determination of non-linearity in the relationship between voltage and current. Although comparable with the dispersion method in sensitivity the non-linearity method has not been developed because of the greater difficulty in adapting it to field use.The testing of installed insulation for discharges in voids involves problems of interpretation and of portability. The nature of these problems is examined particularly in relation to a portable a.c. discharge detector developed for this kind of testing.

 

点击下载:  PDF (1168KB)



返 回