Fouling and corrosion in an open recirculating cooling system
作者:
T S Rao,
M S Eswaran,
V P Venugopalan,
K V K Nair,
P K Mathur,
期刊:
Biofouling
(Taylor Available online 1993)
卷期:
Volume 6,
issue 3
页码: 245-259
ISSN:0892-7014
年代: 1993
DOI:10.1080/08927019309386227
出版商: Taylor & Francis Group
关键词: fouling;MIC;biocide;corrosion inhibitor;carbon steel;recirculating cooling system
数据来源: Taylor
摘要:
The paper discusses the problem of fouling and corrosion in the Service Water System of a nuclear reactor employing an open recirculating cooling system. Field and laboratory experiments were carried out using carbon steel as test material. The studies included corrosion rate measurements, corrosion product characterisation (using XRD, EDAX and IRAS), and the effects of addition of biocide (chlorine) and corrosion inhibitor (polyphosphates) on the bacterial population of the cooling water. The fouling films which developed on metal and glass coupons as well as debris collected from within the cooling system were chemically characterised. The results indicated the prevalence of microbiologically induced corrosion (MIC) within the system. The findings are discussed in the light of the information available on MIC of cooling water systems.