ASSESSMENT OF STORMWATER RUNOFF FOR RECYCLE IN COOLING TOWERS AT KSC, FLORIDA1
作者:
Forrest E. Dierberg,
Krista L. Jones,
期刊:
JAWRA Journal of the American Water Resources Association
(WILEY Available online 1989)
卷期:
Volume 25,
issue 1
页码: 43-47
ISSN:1093-474X
年代: 1989
DOI:10.1111/j.1752-1688.1989.tb05664.x
出版商: Blackwell Publishing Ltd
关键词: rainfall harvesting;runoff;coolant makeup water;Kennedy Space Center;Florida
数据来源: WILEY
摘要:
ABSTRACT:In addition to measuring the quantity of stormwater runoff generated during ten rainfall events from the Vehicle Assembly Building (VAB) area of Kennedy Space Center (KSC), historical rainfall records were also used for determining the feasibility of implementing a program of stormwater recycling to air conditioning cooling towers. It was projected that 0.182 million gallons per day (MGD) of runoff would be generated from the VAR area during a year of average rainfall (48 inches); only 0.117 MGD is required for coolant makeup water in the VAR area. Due to the seasonal variations in rainfall, stormwater recycling may not always meet all the cooling water demands.